Calculation of the permissible load of an induction motor with parametric winding asymmetry
Abstract
The purpose of the research presented in this article is to develop an engineering methodology for determining the permissible load torque of a three-phase asynchronous motor with parametric electromagnetic asymmetry of the stator windings, which ensures that the insulation service life is maintained at an acceptable level.
Based on the full phase (ABC–abc) mathematical model of an induction motor, in which the asymmetrical active resistances and inductances of one of the stator phases are explicitly specified, a numerical simulation was carried out in the MATLAB Simulink environment. Using the temperature-exponential model of insulation ageing, the dependence of the relative service life on the current multiplicity was determined. Using the least squares method, an analytical approximation of the multiplicity of insulation resource reduction as a function of the asymmetry coefficient and load moment was obtained.
It is shown that even moderate asymmetry of the active resistance of the stator phase (±20–30%) leads to a significant increase in currents and copper losses, as well as to a multiple reduction in the insulation resource at nominal load. It is established that a targeted reduction in the load moment by 5–10% of the nominal value allows compensation for the negative impact of asymmetry and returns the insulation resource to unity.
A generalised analytical model of insulation resource reduction is proposed that simultaneously accounts for the parametric asymmetry coefficient and the level of mechanical load, and, based on it, an engineering methodology for calculating the permissible load for partially damaged induction motors is developed.
The results obtained allow operators to make informed decisions about continuing to operate engines with detected parametric asymmetry, and to adjust the load to prevent accelerated thermal ageing of the insulation and unplanned failures.